UPS SOFTWARE FOR 650VA UPS ON NCR 3269
1. INTRODUCTION
Basic Installation procedures for the NCR 650VA UPS on an NCR3269 System using PowerMon II Software V3.2.2.
2. THE FIRST STEP IS TO SETUP THE COMM PORT.(Do not connect the Comm cable yet!)
2.1 SETUP THE SERIAL PORT (COMM PORT 2) TO 2400 BAUD RATE
@root
#mkdev serial and set the baud rate to `K'
Edit the /etc/inittab and the /etc/conf/init.d/sio files accordingly.
set baud rate to `K' on tty2a and tty2A
#enable tty2A
#disable tty2A
#stty
2.2 NOW CONNECT UP THE UPS DATA CABLE TO COMM PORT TWO.
3. NOTE: Two diskettes are included in the software package ONLY diskette #1 is required.
Diskette #1Interactive, SCO UNIX, SCO XENIX, Solaris (Intel), Unix Ware, SVR4
Diskette #2IBM AIX(RISC Systems/6000), Solaris (SPARC), SunOS.
4.
4.1 ENTERroot
#cd /tmp
#tar xvf/dev/fd0
#./install.ups
4.2 Notification of registration is displayed - ignore!
PressSPACE BAR
PressRETURN
4.3 Product information displayed about - ignore!
PowerMon II Software.
PressSPACE BAR
PressRETURN
4.4 Informed that UPS Monitoring Software to be installed in /etc/UPS.d directory
PressRETURN
4.5 THE CONFIGURATION MENU IS DISPLAYED.
CONFIGURATION CODE3
UPS PORT DEVICEtty2A
DEVICE FOR DIAGNOSTIC OUTPUTconsole
SHUTDOWN TIMER180seconds
POLLING INTERVAL1second
STARTING DELAY30seconds
Enable Battery Backup MessagesYES
Broadcasting
First Broadcast10 seconds
Interval Broadcast60 seconds
ENABLE DIALING OUT ON EVENTSNO
4.6 `F8'TO SAVE AND EXIT
4.7 RETURNED TO PowerMon II MAIN MENU
There are numerous options:
1.PowerMon IICONFIGURATION
2.POWER HISTORY
3.LOG OPTIONS
4.ACTIVATION
5.TERMINATION
6.REMOVAL
9.EXIT
`F1'for help.
4.8 RE-BOOT The System To Ensure That PowerMon II Software Is Activated On Power-Up Functionally Test.
4.9 To access PowerMon II Main Menu after installation
From root
#cd /etc/UPS.d
#./upsmenu
4.10 CONFIGURATION CODE
Information concerning the UPS interface and cabling supplied. Code is stamped on the inside front cover of the manual 3
4.11 UPS PORT DEVICE
Serial port that was previously set-up
DO NOT include /dev in component of path
For COMM Port 2 entertty2A
Follow instructions
1. Disconnect data cable
2. connect data cable
3. this sets up `modem' connection to the UPS.
4.12 DEVICE FOR DIAGNOSTIC OUTPUT
Where to display regular diagnostic messages
DO NOT include /dev in component of path
Console
4.13 SHUTDOWN TIMER
Specifies how long software waits after detection of a power-fail before commencing shutdown procedure
Default setting 180 seconds
4.14 POLLING INTERVAL
Indicates how often to poll for UPS status
Default setting 1 second
4.15 STARTING DELAY
Time for software to wait before automatically activating the monitor.
Default setting 120 seconds
SET TO 30 seconds
4.16 ENABLE BATTERY BACKUP MESSAGE BROADCASTING
Display message to users that system running on battery.
WAIT BEFORE FIRST BROADCAST
Time delay before first message. Default setting 10 seconds.
INTERVAL BETWEEN MESSAGES
Time delay between messages. Default setting 60 seconds.
4.17 ENABLE DIALING OUT ON EVENTS
To remotely inform of power failure. Default setting NO.