INFORMATION RELEASE AB 186
POWERMON II UPS SOFTWARE for 650VA UPS on NCR 3269 running UNIX SVR4
Amend the tiltle of AB166 to read:-
UPS software for 650 VA UPS on NCR 3269 running SCO UNIX ONLY
Basic Installation procedures for the NCR 650 UPS on an NCR 3269 running Unix SVR4, using Power Mon II
The correct version of the Power Mon II software comes at present in a box with K519 in its part number and the diskette has MP-RAS Ver 3.2.3 written on it.
Any other part number or version may not work.
NOTE: NCR 3269 together with Power Mon II only have an ORDERLY SHUTDOWN facility, they do not have a POWER FAIL RECOVERY capability.
Setting up the serial port
Installing the communications cable
Installing the utility
The serial port must use tty01
Ensure that no service is running on the port. If there is one running then remove it.
Enter pmadm -l | pg <CR> to display Port Services.
Enter y <CR>
Installation Directory = /etc/UPS.d
Cable type =3 - or details inside front cover of manual
Serial Port = /dev/tty01
Diagnostic device = console
Shutdown Timer = 180 seconds
Shutdown Type = orderly stystem shutdown
Polling Interval = 1 second
Startup Delay = 120 seconds
Message Broadcasting Enabled = Yes
Message Broadcasting Wait = 10 seconds
Message Broadcast Interval = 60 seconds
Dialing Out on events Enabled = No
Do you wish to rebuild kernel after installation y
Do you wish to automatically start to monitor UPS after installation y
cd /etc/UPS.d <CR> to access working directory
./upsmenu <CR>
Power Mon II