Back to Contents Page

Specifications: Dell® PowerEdge® Rack-Mountable Solutions Installation Guide

Dimensions | Physical and Environmental Specifications


Dimensions

Fig5-01.gif (35062 bytes)


Table 1. Physical and Environmental Specifications 
Physical
Height 218.0 cm (84.84 inches)
Width 60.0 cm (23.62 inches)
Depth 85.0 cm (33.46 inches)
Weight 127 kg (280 lb) empty. Maximum allowable weight of internal components is 453.6 kg (1000 lb).
Environmental
Temperature:
      Operating 10 to 35C (50 to 95F)
      Storage -40 to 65C (-40 to 149F)
      Relative humidity 8% to 80% (noncondensing)
Maximum vibration:
      Operating 0.25 G at 3 to 200 Hz for 30 min
      Storage 0.5 G at 3 to 200 Hz for 30 min
Maximum shock:
     Operating half-sine wave form: 38 G for 2 ms
      Storage half-sine wave form: 83 G for 2 ms;
square wave form: 20 G for 35 ms
Altitude:
      Operating -16 to 3048 m (-50 to 10,000 ft)
      Storage -16 to 10,600 m (-50 to 35,000 ft)

Back to Contents Page