FECO LVC # 5
![]() |
FECO: |
LVC # 5 |
MODIFICATION NO: |
N/A | |
PRODUCT: |
MOPUPS UPS SOFTWARE | |
SUB-ASSEMBLY: |
N/A | |
ESTIMATED MAN HOURS: |
N/A | |
CLASS OF CHANGE: |
INFORMATIONAL | |
REASON FOR CHANGE: |
LISTING SET UP INSTRUCTIONS | |
RELATED FECO/AB |
N/A |
SETUP INSTRUCTIONS FOR MOPUPS UPS SOFTWARE
1. | INTRODUCTION | |||
|
MopUPS version 1.2 is power fail recovery UPS
software |
|||
2.
|
INSTALLATION |
|||
2.1
|
MopUPS comes on a diskette |
|||
2.2 | Load the diskette by : | |||
|
pkgadd Ñ -d Ñ diskette 1 | |||
2.3 | Responses to prompts are : | |||
Enter name of directory | Default | /opt/mopups | ||
Would you like MopUPS to start | y | |||
If you intend to use /dev/tty/01 to monitor and
the port is not setup, MopUPS to add this port for you? |
y | |||
Rebuild kernel? | y | |||
|
Would you like to reboot? |
y | ||
2.4
|
Then there is the opportunity to allow you to
check and change any parameters set so far |
|||
2.5 | When completed the display will read | |||
|
Installation of <MopUPS> was successful |
2.6
|
To set delays etc. at root prompt Enter mopups
Ñ config
|
2.7
|
To start enter : mopups Ñ
start
<CR>
this sets the daemon running |
3.
|
Screen display |
MopUPS for UNIX Configuration |
||||||||
Port parameters | Delay parameters | |||||||
> | Device | /dev/tty/01 | Delay | Repeat | ||||
[ ]> | 1200 | 7E1 | Notify | 120 | 0 | |||
[X] | 9600 | 8N1 | Warning | 300 | 30 | |||
[ ] | Other | |||||||
Speed: | 9600 | |||||||
Cable disconnect: | 300 | |||||||
Parity: | None | |||||||
Word Size: | 8 | UPS Poweroff: | 120 | |||||
Stop bits: | 1 | UPS polling: | 15 |
Keystroke summary | ||
[ENTER] or [TAB] | Move to next field, leaves entry as is | |
[ESC] | Aborts input in that field | |
[BS] or [DEL] | Removes last character typed | |
[CTRL]-[D] or [CTRL]-[W] | Exit configuration editor, you can then choose to update with y | |
4. |
To test communications to UPS, Enter mopups Ñ test | |
5. |
To stop daemon, Enter mopups Ñ stop | |
6. |
To start daemon, Enter mopups Ñ start | |
7. |
To stop and start after re-configuration change, Enter mopups Ñ restart | |
8. |
To get report, Enter mopups Ñ report | |
9. |
To get version installed, Enter mopups Ñ info |
10. |
Carry out test of Powerfail Recovery | |
10.1 |
Ensure that MopUPS is installed on the system, and that the UPS is powering the system, and the data cable is connected between the UPS and the system. | |
10.2 |
Remove the mains input to the UPS | |
10.3 | MopUPS is invoked and will begin to shut the system down. Messages will be displayed : | |
Xx secs Notify powerfail | ||
Users not notified | ||
Notify users | ||
Memory dump slices 0, 1, 2, 3 | ||
Shutting down | ||
10.4 |
The system will completely shut down | |
10.5 |
Replace the mains input to the UPS | |
10.6 |
When system restarts, messages appear detailing the system boot, the restoration of slices 0, 1, 2, 3 and running up in UNIX | |
10.7 | Ensure the system returns to the point where it was prior to the mains failure. |