FECO LVC # 5

FECO:

LVC # 5

MODIFICATION NO:

N/A

PRODUCT:

MOPUPS UPS SOFTWARE

SUB-ASSEMBLY:

N/A

ESTIMATED MAN HOURS:

N/A

CLASS OF CHANGE:

INFORMATIONAL

REASON FOR CHANGE:

LISTING SET UP INSTRUCTIONS

RELATED FECO/AB

N/A

SETUP INSTRUCTIONS FOR MOPUPS UPS SOFTWARE

1. INTRODUCTION
 

 

MopUPS version 1.2 is power fail recovery UPS software
2.

 

INSTALLATION
2.1

 

MopUPS comes on a diskette
2.2 Load the diskette by :
 

 


pkgadd Ñ -d Ñ diskette 1
2.3 Responses to prompts are :
Enter name of directory Default /opt/mopups
Would you like MopUPS to start y
If you intend to use /dev/tty/01 to monitor and the port is not setup,

MopUPS to add this port for you?

y
Rebuild kernel? y
 

 

Would you like to reboot?
y
2.4

 

Then there is the opportunity to allow you to check and change any parameters set so far
2.5 When completed the display will read
 

 

Installation of <MopUPS> was successful
2.6

 

To set delays etc. at root prompt Enter mopups Ñ config
2.7

 

To start enter : mopups Ñ start <CR> this sets the daemon running
3.

 

Screen display

MopUPS for UNIX – Configuration

Port parameters Delay parameters
 > Device /dev/tty/01 Delay Repeat
[ ]> 1200 7E1 Notify 120 0
[X] 9600 8N1 Warning 300 30
[ ] Other
Speed: 9600
Cable disconnect: 300
Parity: None
Word Size: 8 UPS Poweroff: 120
Stop bits: 1 UPS polling: 15
Keystroke summary
[ENTER] or [TAB] Move to next field, leaves entry as is
[ESC] Aborts input in that field
[BS] or [DEL] Removes last character typed

[CTRL]-[D] or [CTRL]-[W] Exit configuration editor, you can then choose to update with y
4.
To test communications to UPS, Enter mopups Ñ test
5.
To stop daemon, Enter mopups Ñ stop
6.
To start daemon, Enter mopups Ñ start
7.
To stop and start after re-configuration change, Enter mopups Ñ restart
8.
To get report, Enter mopups Ñ report
9.
To get version installed, Enter mopups Ñ info
10.
Carry out test of Powerfail Recovery
10.1
Ensure that MopUPS is installed on the system, and that the UPS is powering the system, and the data cable is connected between the UPS and the system.
10.2
Remove the mains input to the UPS
10.3 MopUPS is invoked and will begin to shut the system down. Messages will be displayed :
Xx secs Notify powerfail
Users not notified
Notify users
Memory dump slices 0, 1, 2, 3
Shutting down
10.4
The system will completely shut down
10.5
Replace the mains input to the UPS
10.6
When system restarts, messages appear detailing the system boot, the restoration of slices 0, 1, 2, 3 and running up in UNIX
10.7 Ensure the system returns to the point where it was prior to the mains failure.