LVC # 10

 

edplogo.gif (5330 bytes)

FECO:

LVC # 10

MODIFICATION NO:

N/A

PRODUCT:

POWER MON II on NCR 4091 UPS

SUB-ASSEMBLY:

UNIX SVR4 03.02.xx

ESTIMATED MAN HOURS:

N/A

CLASS OF CHANGE:

INFORMATIONAL

REASON FOR CHANGE:

INTRODUCTION OF POWER FAIL RECOVERY WITH NCR 4091 UPS

RELATED FECO/AB

LVC # 8

POWER FAIL RECOVERY

POWERMON II UPS SOFTWARE for NCR 4091, UPS on NCR S20, S40, or 4300 running UNIX SVR4 03.02.xx

1.        NOTE:

Throughout this FECO a SPACE in a string is shown by a Ñ

All other spaces are purely cosmetic.

2.        INTRODUCTION

Basic Installation procedures for PowerMon II with the NCR 4091 UPS on an NCR S20, S40 or
4300 running Unix SVR4. Ver 03.02.xx to provide a Power Fail Recovery facility.
On the NCR 4300, PowerMon II is designed to be installed onto a system that does not have the
internal UPS system fitted.
Power Fail Recovery is known not to function on an NCR 3416, 3259 or 3269.
The correct version of the PowerMon II software comes at present in a box with K519 in its part
number and the diskette has MP-RAS Ver 3.2.3 written on it.

Any other part number or version may not work.

3.      If Powermon II is being installed onto an existing installed system, then a Project Plan must
         be produced and approved prior to this installation. Before installation of Powermon II, ensure that the customer has two full
         verified file saves
.

4.        Installation and configuration consists of the following:

5.        SYSTEM

6.        SERIAL PORT

The serial port must use tty01

Ensure that no service is running on the port. If there is one running then remove it.

Enter pmadm Ñ -l Ñ | Ñ pg <CR> to display Port Services.

7.       STRATEGY

Ensure that the strategy is Power Fail Recovery.
To display the strategy in root
Enter strategy and ensure response is Current Strategy is Power Fail Recovery.
If it is Orderly Shutdown, then change it to Power Fail Recovery.
Enter # strategy Ñ -s <CR>

8.       COMMUNICATIONS CABLE

Connect the communications cable between the UPS and the NCR 3000 COM 2 port.
This should be the correct type of cable for the appropriate UPS used.
For Powerware Prestige (NCR4091) use Cable Type JT or JU1.

9.      INSTALLATION OF POWERMON II

9.1     On the system login to root

9.2     Enter pkgadd Ñ -d Ñ diskette1 <CR>

9.3     Insert the diskette into the floppy drive

9.4     Enter go <CR> & follow all the prompts to install the software.
           When prompted to select the packages, select all.

9.5      The software will load and display the configuration screen similar to the one below.

9.6       At prompt do you wish to modify them at this time? Enter y <CR>

9.7       Select the options listed below as the EDP standard setting:

Installation Directory =                                          /etc/ups.D
Cable type =                                                  
      3 - Or Details Inside Front Cover Of Manual
Diagnostic device =                                              console
Shutdown Timer =                                                180 seconds ***
Shutdown Type =                                                 Power Fail Recovery
Polling Interval =                                                   1 second
Startup Delay =                                                    120 seconds
Message Broadcasting Enabled =                         yes
Message Broadcasting Wait =                              10 seconds
Message Broadcast Interval =                               60 seconds
Dialing Out on events Enabled =                           no

Do you wish to rebuild kernel after installation                                         Y
Do you wish to automatically start to monitor UPS after installation          N

***The EDP standard (default) setting is 180 secs.
Please refer to para 14 for the latest setting for the type of system used.

9.8.     Follow prompts and reboot the system, removing the diskette first.

CONTROL CENTRE

10.1    The Control Centre can be used to view and alter settings, start or stop Power Mon, and
            view history

10.2     When the system has run up again, run the control centre to check settings.

10.3     Login to root and enter

cd Ñ /etc/UPS.d <CR> to access working directory

10.4     Start the Control Centre by entering

./upsmenu <CR>

10.5     The following Control Centre Screen will appear:-

 image1_lvc_10.gif (160990 bytes)

10.6   Select configuration and the following screen will appear

image_2_lvc_10.gif (164414 bytes)

10.7     Check all entries are correct

10.8     When they are, press F8 to exit, Save and Start Power Mon II.
             This will start the Power Mon II.

10.9     Select 9 Exit Powermon II menu

11.    TO RESET UV PROCESSES

    11.1     Enter UV setup

    11.2     Select Option 2 Maintain Process Records

    11.3     Reset PROCESS and LINE INFORMATION

    Select R for Reset
    Select * for all
    Select U for unconditioned
    Select E for exit

    11.4     Select 0 for exit from UV set up.

12.    TEST POWER FAIL RECOVERY

    12.1     Ensure that several screens are logged into an application.

    12.2     SHORT MAINS FAILURE

    12.2.1  Switch OFF the mains input into the UPS, to simulate a short mains failure.

    12.2.2  Check that: the message "ON BACKUP POWER" is broadcast to all screens, with a time
                 when the system will shutdown.

    12.2.3  Restore the power to the UPS before this time

    12.2.4  Ensure message POWER RESTORED. Is displayed and that everything continues as it was
                 before the mains failure.

    12.3     LONG MAINS FAILURE

    12.3.1  Switch OFF the mains input into the UPS, to simulate a long mains failure.

    12.3.2  Check that the message "ON BACK UP POWER " is broadcast to all screens with a time when the system will
                shutdown. After this time, on the system console, it should show it transferring memory slices, then after this the
                statement, "SHUTTING OFF UPS".

    12.3.3  The system and the UPS will NOT Shut Off; but after the last message the screen will paint a
                dot every few seconds, and slowly fill up the screen with these dots. This will continue until either the power is
                restored or the UPS battery runs out of power.

    12.3.4  For test purposes, wait two minutes then restore the mains power to the UPS.

    12.3.5  Ensure that the system runs up correctly that the messages are displayed on the console
               showing memory slices being restored. And that the screens return to the point they were
               before the "Mains Failure". You may have to press <CR>.

    12.4      Testing Complete

13.    REMOVAL POWER MON II

13.1     Log to root

13.2     Enter pkgrm Ñ PMII

13.3     Do you want to remove this package Y

13.4     Do you wish to automatically rebuild the kernel after the UPS driver has been removed Y

13.5     At # prompt reboot the system, Enter shutdown –y Ñ -g0 Ñ -i6

14.     LATEST SETTINGS ***
                       For S20 systems the Shutdown Timer should be set to 480 secs.

Return to Index