FECO LVC # 9/1
![]() |
FECO: |
LVC # 9/1 |
MODIFICATION NO: |
N/A | |
PRODUCT: |
Failsafe/Lansafe III software Version 4.06 | |
SUB-ASSEMBLY: |
4091 UPS, Running on Unix SVR4 03.02.xx | |
ESTIMATED MAN HOURS: |
N/A | |
CLASS OF CHANGE: |
Informational | |
REASON FOR CHANGE: |
Introduction of updated product | |
RELATED FECO/AB |
LCV # 4 LVC # 8 |
INTRODUCTION OF FAILSAFE/LANSAFE III SOFTWARE V 4.06
For use on NCR4091 UPS with systems running Unix SVR4 03.02.xx
This FECO supercedes FECO LVC # 4.
It is for use with the following operating systems.
HP-UXâ | Novellâ NetWareâ | DOS |
IBM AIXâ | Novellâ Manage Wise | DEC UNIX |
Interactive UNIXâ | OS/2â and OS/2 Warp | UNIX Ware |
SCO UNIX | WindowsÔ 3.x | Windows NT |
Solarisâ and SunOSâ | Windows 95 | Macintosh |
AT&T UNIX | Linux |
This FECO only details the use with Unix SVR4 03.02
NOTE Throughout this FECO a space in a string is shown by a Ñ .
All other spaces are purely cosmetic.
4.1 Dump Slice
On the system ensure that there is a dump slice on the disk, and that its size is adequate for the amount of memory in the machine.
4.2 The ups_status File
The ups_status file contains UPS-OFF or UPS-ON. If the file contains UPS-OFF; at power fail it attempts to log out of UniVision, down dating the other UV control files as it exits. If it completes this task successfully, the process returns to the UNIX login. If ups_status does not exist the system defaults to UPS-OFF.
The ups_status file is located in the ./UniVision/univision/admin directory.
To configure ups_status, login to SYSPROG and enter !<CR>. At the UNIX prompt ($) enter UVups<CR>.
If ups-status does not exist the system prompts:
Current ups_status setting = xxx.xxx
Do you want to continue with the change file? (Y/N):
Enter Y <CR>
File "univision/admin/ups_status" not found or of zero size
Do you want to create the file? (Y/N)
Enter Y <CR>
If you enter Y the file is created and the system prompts you as follows:
Enter "0" to set UPS_OFF or "1" to set UPS-ON:
If you enter 1 you get the following message:
New setting of "ups_status" = UPS=ON
NOTE For Orderly Shutdown, the ups_status file must either NOT EXIST or if it does it MUST BE set to UPS_OFF.
4.3 SERIAL PORT
The serial port must use tty01
Ensure that no service is running on the port. If there is one running then remove it.
Enter pmadm Ñ -l Ñ | Ñ pg <CR> to display Port Services.
4.4 Ensure that the strategy is Orderly Shutdown.
To display the strategy in root
Enter strategy and ensure response is Current Strategy is Orderly Shutdown.
If it is Power Fail Recovery, then change it to Orderly Shutdown.
Enter # strategy Ñ -s <CR>
4.5 Connect the communications cable between the UPS and the
NCR 3000 COM 2 port.
This should be the correct type of cable
for the appropriate UPS used.
For Powerware Prestige (NCR4091) use
Cable Type JM.
5.1 Insert the CD, Failsafe/Lansafe III release 4.06 into the CD drive.
5.2 In root mount the cd.
Enter
# mount Ñ -FÑ cdfs Ñ -o Ñ r o, nmconv = c, fperm = 500 Ñ /dev/cd0 Ñ /cdrom
5.3 Change directory to the mounted point for the cd, Enter
# cdÑ /cdrom
5.4 Run the install script, Enter.
# shÑ ./INSTALL.SH
Welcome <CR>
Respond to the prompts as shown below in bold.
Continue installation? Y
Are you installing from a CD - ROM ? Y
The default install pathname for this softwre is /usr/ls3
Do you want to change this path N
Automatically run Lansafe III on start up Y
The screen will list the install parameters
Check they are correct
Are these install parameters acceptable Y
This system will install Lansafe III
If the system is the only one being run off of the UPS then the answer N to the following question.
Is this computer part of a UPS group N
Is this computer the (C)ontroller or (M)ember. Usually Enter C
Please enter the UPS model Enter 1 for Netups
Enter 4 for Powerware
Prestige (NCR4091)
Enter 13 for 9110
Or relevant number
Please enter the UPS port Enter 3 for
None Of The Above,
then Enter
/dev/tty01
Please enter the Wink Time (1-999 secs) Enter 5
(Wink time is the number of seconds wait after a power
failure, before a message is displayed)
Please enter the Power Failure Countdown Time (1 -999min) Enter 5
(Delay time after power failure before Shut down commences)
Please enter the time needed to Shut Down System (1 -999sec) Enter 180
(If it is required that any of the above need to be changed to
customer requirements the changes are to be noted and stored
with the fault log on site)
Please enter the UPS Access Code Enter edp
-this will not appear on the screen
Please re-enter the UPS Access Code for verification Enter edp
Lansafe III configuration completed successfully
Press <CR> to continue
5.5 To initialize the software, in root
Enter # cdÑ /usr/ls3
Enter # ./ls3& to start demon
6 SERVICING TESTS/FUNCTIONS
6.1 Servicing tests and functions are carried out via the Power Monitor Menu
6.2 To access the Power Monitor Menu from root
Enter # ./usr/ls3/ls3con
Please enter the Access Code for the Power Monitor
Enter edp
6.3 POWER MONITOR MENU
O Exit
1. Configure Lansafe
2. Start hardware test
3. Start preventive maintenance
4. Shutdown/reboot workstation
5. View Output load, Input utility power and battery
6. Export power and battery log files Power Monitor Menu Description
1. To reconfigure or change the access code
2. Dependant upon type of UPS.
3. Same as 2
4. Submenu displayed
O exit
1 Timed shutdown
2 Reboot
3 Permanent shutdown
4 Unload software - note this only stops the daemon running and does not remove
the software from system
To remove the software see para 8
List details of current (as of now) status Exports file to printer etc.
7 FUNCTIONAL TEST
7.1 To carry out a functional test, remove the mains input supply to the UPS.
7.2 Ensure that a message is displayed on the system console and that the system runs down
7.3 When the system has run down wait until the UPS switches off.
7.4 Reconnect the mains supply to the UPS.
7.5 Ensure that the system runs up correctly, the system ON switch may have to be operated.
7.6 NOTE. Under normal operating conditions, if the mains supply to the
UPS is reconnected to the UPS after
system has run down but before UPS
switches off; then the system must be switched off before it will run
up again.
8 TO REMOVE THE SOFTWARE
8.1 Identify the pid number for the associated Failsafe/Lansafe III
software
In root Enter # ps Ñ ef Ñ |Ñ
grep Ñ ls3
Kill this pid Enter # kill Ñ 9Ñ pid number Remove all the contents of the associated Failsafe/Lansafe III software directory
In root Enter # cd Ñ /usr/ls3 to go to the ls3 directory
Enter # r m Ñ r Ñ * to remove the contents of the ls3 directoryReturn to rootEnter cd Ñ /Remove the directory
Enter # r m d i r Ñ ls3The Software removal is complete
9. CABLE SPEC
Cable to connect the system com2 port to the UPS, designated as Cable Type JM